Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
​What happens when you remove a rating plug from a Micrologic trip unit?
Issue:
Removal of rating plug from a Micrologic Trip Unit

Product Line:
Molded Case Circuit Breakers / Air Circuit Breakers

Resolution:
Removing the rating plug from the Micrologic trip unit automatically reduces the rating of the breaker to value of 40% (e.g. a 1000 A breaker becomes a 400 A breaker).
This applies to the following breakers and trip units:

Circuit Breakers
PowerPacT P and R
MasterPact NT and NW

Micrologic Trip Units
Standard 2.0, 3.0, 5.0
Ammeter 2.0A, 3.0A, 5.0A, 6.0A
Power 5.0P, 6.0P
Harmonic 5.0H, 6.0H

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings