Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
On the ATV930 and other drives, would the torque measurement be affected by the presence of a sine wave filter between the drive and the motor?
Issue:
Torque Measurement when using Sine Wave Filters.

Product Line:
ATV630, ATV930, ATV71, ATV61, ATV320, ATV32, ATV312

Environment:
All

Cause:
NA

Resolution:
The torque measurement will not be affected by the presence of a sine wave filter between the drive and the motor. Actually, it makes torque measurement's value better.
The current scope will be actual SIN/COS wave with sine wave filter. Without sine wave filter, the output current will have some peak value, which probably affects the accuracy of current.
The torque is directly proportional to current (M∝I).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings