Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Does OFS recognize the bit rank of a DDT (Derive Data Type)?
Issue:
Does OFS recognize the bit rank of a DDT (Derive Data Type)?

Product Line:
OPC Factory Server

Resolution:
OFS does not support bit ranks of a DDT.  Unity is not able to export the overloaded comments of DDT members instance (bit rank).  It was to make the data dictionary as light as possible.

Two possible workaround :
-  access the extracted bit via the complete syntax ddt_inst.int.bit
-  move the Bit rank to a Bool variable

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings