When do the heatsink fans run on the ATV61 / ATV71 series drives?


Heat sink fan operation differs depending on the frame size of the drive:
- for size 2 to 5B drives, fans start when the drive thermal state reaches a temperature level --> THD parameter = 70%.  The fans turns off when drive thermal state is less than 60%
- for size 6 to 8 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 1 minute after the run command is removed.
- for size 9 to 15 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 10 minutes after the run command is removed.

For example, an ATV61HD18M3X drive (size 6), the heatsink fan starts when a Run command is given.

d
Here is a table indicating what drives are included for each Frame size:
s
NOTE that the frame sizes listed are the global engineering frame sizes.  Some documents from the US may have slightly different labels.

*******

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings