Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Does the M580 Hot Standby CPU's support %SW60 - 65 and %SW69 ?
No. These words are dedicated to the Unity Quantum HSBY solution.
The M580 uses a DDT (Device Data Type) which is automatically created when selecting an M580 HSBY processor in Control Expert (formerly Unity Pro)..

The DDT is named ECPU_HSBY_1. All of the functionality and status information offered by %SW60 - 65 for Quantum HSBY is made
available through this DDT for M580 HSBY user.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings