Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
The 4202-DR or 4202-DS flashes S6 ERROR (5G, SG or 56) and then the display goes blank.

This is a normal part of the boot up sequence when there is no flow computer C program installed. This will happen after a cold boot or if the RAM battery has failed and it has lost it's C program.

You will need to connect to the 4202 with RealFLO, install a flow computer and a configuration that has elements setup for the Display Module. The Display Module depends on how the flow computer is configured so if nothing is configured, it won't display anything.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings