Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
When is arc-flash mitigation required by the NEC?
Issue:
NEC and Arc-Flash Mitigation

Product Line:
Circuit Breakers

Environment:
Powerpact and Masterpact

Resolution:
In the 2017 edition of the NEC, article 240.87, arc energy reduction is required where the highest continuous current trip setting for which the actual overcurrent device installed in a circuit breaker is rated or can be adjusted is 1200 A or higher. This means that even if an electronic trip circuit breaker with a 1200 A sensor has its current rating switch set to, for example, 0.75 (900 A), it will still require an arc energy reduction means. If the overcurrent device in the circuit breaker meets this criterion, then documentation and a method to reduce the clearing time must be provided.

See attached data bulletin for more information.

For information on the Schneider approved arc flash mitigation system, ERMS, see second attachment.

Schneider Electric USA

Attachment(s)
ERMS - NHA67346 .pdf [10.46 MB]
NEC 2023 Arc Energy Reduction 0760DB1402.pdf [115.65 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings