Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to Set OPC Tag Scanning Rate in PowerSCADA Expert
Issue
To better tune the system.

Product Line
PowerSCADA Expert, PSE (all versions)

Environment
OPC

Cause
To be able to control how fast OPC tags can be scanned.

Resolution
ScanRate is the parameter that controls how fast tags are being scanned.
Assuming that the tags are to be scanned once every second (1000 millisecond), add the following in Citect.INI file:
[OPC]
ScanRate = 1000

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings