Per the NEC, what are the standard ampere ratings of fixed-trip circuit breakers (600Vac maximum)?
Issue:
Where do circuit breaker amp ratings come from?

Product Line:
Circuit Breakers

Resolution:
Per NEC 240.6, the standard ampere rating for inverse time, fixed-trip circuit breakers, 600Vac maximum, shall be considered as follows:
15202530354045
5060708090100110
125150175200225250300
350400450500600700800
1000120016002000250030004000
50006000

The use of inverse time circuit breakers with nonstandard ampere ratings shall be permitted.