Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Remote Display Cable Pinouts for CM3, CM4, and PM8 Series Meters
Issue
Customer may need to know the pinout for the remote display cables for the PM8, CM3, and/or CM4 meters

Product Line
CM3000
CM4000
PM800

Environment
Cabling Pinout

Resolution
The CM3000, CM4000, and PM800 all use the same display cable, whose current part numbers are CAB4 (4' length), CAB12 (12' length), and CAB 30 (30' length).
These display cables utilize a 6 pin RJ-11 jack with 26 AWG wire.
They are RS-232, so 50ft is the maximum length.
The pinout is shown below:
diagram

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings