Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
ENM 8.3 SEEG.exe error while trying to refresh tags, dll file has already loaded from a different location

Issue
After applying a patch to ENM, user cannot refresh tags. The error message suggests a service is not running however all services are running. In the ENM event log the following message is included
"API restriction: The assembly 'file:///C:\Program Files (x86)\Schneider Electric\StruxureWare Solutions\Event Gathering Service\[some file name].dll' has already loaded from a different location. It cannot be loaded from a new location within the same app domain.

Product Line

Power Monitoring Expert 7.2

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024



Environment
Applying patch to update dll file

Resolution
The likely cause is because the updated dll and original dll (with a different name) are in the same folder. Move the old dll file to a new location and restart the Event Gathering Service.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings