EM4805 meter displays Line to Neutral voltage rather than Line to Line

Issue

User want to know the the rated voltage of the EM485 meter Display settings.

Product Line
EM4805 meter

Environment
Reading voltage from EM4805 meter

Cause
EM4800 meter is reading Line to Neutral voltage rather than showing Line to Line voltage.

Resolution
If the EM4805 meter is wired as wye system, then meter will show L-N (Line to Neutral) voltage.
If the EM4805 meter is wired as delta system, then meter will show L-L (Line to Line) voltage.