What are the RF limits for QO and HOM breakers with suffixes AFI, CAFI, DF, GFI, EPD and EDB-EPD breakers?
Issue:
RF limits for EDB-EPD​ breakers, and HOM and QO arc-fault and ground-fault protection breakers with suffixes AFI, CAFI, DF, GFI, EPD​​​​​​

Product Line:
Circuit Breakers

Resolution:
All of these products are required to withstand the following:
3 volts/meter radiated intensity between 80 MHz – 1 GHz
3 volts conducted intensity between 150 kHz – 80 MHz

There is a risk of tripping any time the above limits are exceeded.