Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the minimum voltage rating for DC Bus fuses on Altivar drives?

Article available in these languages: Spanish

Issue:
What is the min voltage rating for DC Bus fuses?

Product line:
ATV71, ATV312, ATV320, ATV930

Environment:
All

Cause:
Power is supplied directly to the Altivar DC bus and fuse protection is recommended.

Resolution:
With Line supply voltage of 230-400Vac, use 690Vdc rated fuses.
With Line supply voltage of 440-480Vac, use 800Vdc rated fuses.
With Line supply voltage of 500-690Vac, use 1000Vdc rated fuses.

Schneider Electric USA

Attachment(s)
DC bus fuses.jpg [13.7 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings