Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I access the Com Scanner Input and Output tables on the Altivar Process Drive?

Article available in these languages: Finnish

Issue:
Access the Comm Scanner Input and Output tables on the Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
To configure the Comm. Scanner (Input/Output) tables:

Resolution:
Programming from the Drive:

  • [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner input]
    • Up to 8 input registers can be configured
    • By default the first 2 registers are pre-configured
      • [Scan. IN1 address] nMA1 - 3201 (EtA Status word)
      • [Scan. IN2 address] nMA2 - 8604 (rFrd - Output frequency)
  • [Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner output]
    • Up to 8 output registers can be configured
    • By default the first 2 registers are pre-configured
      • [Scan.Out1 address] nCA1 - 8501(CMd word)
      • [Scan.Out2 address] nCA2 - 8602(LFrd - Output freq in rpm)




Programming from Somove:

  • [Parameter List] [Fieldbus] [Port - Modbus Serial] [Modbus Fieldbus]

screenshot

NOTE: This is not the same as the I/O scanning table that is used with Ethernet communications.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings