Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What happens if the HMIG5U/HMIG5U2 is used in operating environment temperatures higher than what it is rated for?
Issue:
Looking for some of the behaviors of the HMIG5U/HMIG5U2 as the temperature goes beyond the suggested operating temperatures.

Product Line:
HMIG5U, HMIG5U2

Resolution:

The HMIG5U has a maximum operating environment temperature of 60 degrees Celcius.

When the HMIG5U is used in an operating environment temperature greater than what it is rated for, the following occurs:

at 65 degrees Celcius, the screen brightness becomes a little dark
at 70 degrees Celcius, the screen brightness becomes even more dark
at 75 degrees Celcius, the screen brightness is completely dark
at 80 degrees Celcius, thermal shutdown occurs.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings