Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the BTU for the EX225T3H at no load to full load?
Issue:
What is the heat loss in BTU for the EX225T3H at no load to full load?

Product Line:
General Purpose Dry Type 600 Volts and Below,  EX

Environment:
EX225T3H

Resolution:
Per the Low Voltage Distribution Transformers Catalog 7400CT1501, page 11 provided the core loss from No Load to Full Load
No Load: 328 watts
1/6 load = 445 watts /1517 BTUs/Hr
1/4 load = 590 watts / 2014 BTUs/Hr:
1/2 load = 1378 watts / 4700 BTUs/Hr:
3/4 load = 2689 watts / 9176 BTUs/Hr:
Full watts = 4526 watts / 15443  BTUs/Hr.

Schneider Electric USA

Attachment(s)
7400CT1501.pdf [3.8 MB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings