Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Unable to use a Unity Momentum I/O Scanner service through a router
Issue
The Unity Momentum PLC could not communicate through a router with its I/O Scanner service.

The PLC could not I/O Scan through a router because it did not ARP for its Gateway Address.  This issue was resolved in a firmware fix.


Product Line
171CBU98090
171CBU98091


Resolution
Firmware version affected: 1.0

Issue is resolved in firmware versions:
Patch version 1.1
Released version 1.2 and higher

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings