Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Where are the communication settings of the ECC21 (CM3000/CM4000) saved?
Issue
Customer is trying to swap ECC21 card on CM4000 meter and is asking if the communication settings (e.g. IP address) for ECC21 card are stored on the ECC21 card itself or on the CM4000 meter to know if it will require him to re-program the communication settings or not after the swap.

Product Line
CM4000
CM4250
CM4000T

Environment
Ethernet Communications

Resolution
The communication settings are stored on the CM4000 meter, not on the ECC21 card. Swapping ECC21 card on CM4000 meter will not require to re-program the IP address and other settings for that meter.

Note
The IP address is stored on the meter and there is a continuous interrogation between meter and ECC21 card to make sure that it has not been changed. If the address is changed from the web page it is pushed to the meter, if it is changed from the meter it is pushed to the card

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings