Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
At what height level should Circuit breaker and Fusible switch panels, be installed at?
Issue:
Required height for installing panels, switchboard and breakers.

Product Line:
NQ/NF/I Line/QMB

Environment:
Installation

Resolution:
The NEC does not mandate a minimum mounting height for panelboards, breakers, disconnects, or meter enclosures. But fusible switches, and circuit breakers used as switches, shall be installed so the center of the grip of the operating handle of the switch or circuit breaker, when in its highest position, is not more than 6 ft 7 in.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings