Question:
Does 140NOE77110 work with 140CPU67160 as we found it not able to configure(grey out) in UP11?

Answer:
140NOE77110 works with 140CPU67160 in hardware perspective.
UP11 masks this selection since 140NOE77110 is obsolete & 140NOE77111 is the alternative module.
If customer uses UP3.0, he could configure the 140NOE77110 with 140CPU67160.