Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
EGX300 web page cannot be found

Issue
When trying to open EGX300 web page using IP address, it'll display error "HTTP 404 page not found" after entering correct username and password
IP Address and error
Product Line
EGX300

Environment
HTTP server/Web pages

Cause
This issue possibly happens when file system (Memory) is corrupted

Resolution
Steps to troubleshoot and verify if file system is corrupted:

1) Login to EGX300 using FTP. In Windows you can do that by opening a windows browser and type:
ftp://[EGX 300 IP address] and enter username and password.
You'll notice all files/folders are gone. FTP is empty.

2) Open a web browser and access EGX300 using it's IP address.
after entering correct username and password, it'll display error "HTTP 404 page not found"
Modify your address to the following:
[EGX300 IP Address]/index.shtml

You'll be able to see a corrupted EGX300 web pages, like the image below:
EGX config
Click on "Diagnostics" tab and scroll down to "File System" section
EGX config

You'll notice Total space and free space = 0 KBytes
corruption verification

That confirms that memory is corrupted. In this case, Gateway will need to be RMA'ed

If File System space is not showing as 0 KBytes, follow normal procedure for EGX300 firmware upgrade to upload a new copy of disk image to the gateway
Firmware upgrade process can be found in FA212757

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings