Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
ATS01N222RT Can you do a soft stop?
Issue:
How do I get the ATS01 to soft stop?

Product Line:
ATS01 Altistart 01 Altivar

Environment:
ATS01.....RT

Cause:
Need soft stopping.

Resolve:
If you have a jumper between LI2 and LI+ terminals, you will have soft starting with line power and a coast to stop when line power is removed.

If you have a start-stop signal that closes LI2 to LI+ to start, it will soft start according to the start dial.  When you open this contact it will soft stop (decelerate) according to the stop dial setting.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings