Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can you replace a Q2L main breaker, on a NQOD panel, with the QBL,QDL, or QGL breaker?
Issue:
QB,QD,QGL breakers are suitable for replacing the Q2L main breaker, on a NQOD panel

Product Line:
NQOD Panelboards

Environment:
Panelboards

Resolution:
Technically they fit, however, the UL listing on the NQODQ2 is strictly for Q2 frame breakers. It is possible they will void UL using the powerpact Q frame breakers in them. It will be up
to the panel owner/installer to determine if UL is an issue. When we made the breaker change, it was recommended to replace the NQODQ2 with the NQODQB which was specifically for
the Powerpact breakers but those are now obsolete as well. We no longer offer any main breaker kits for the NQOD panelboards. If a main breaker kit is required for replacing the main,
upgrade to current style NQ panelboard.

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings