Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How is the OPR parameter scaled on the ATV71 series drive?

Article available in these languages: Spanish

Issue:
Scaling the Analog Output when using Output Power on an ATV61/71.

Product Line:
ATV61/ATV71

Environment:
All models, All serial numbers

Cause:
N/A

Resolution:
The output power (OPR) function is scaled between 0 and 2.5X the NPR (Rated motor power) setting under menu 1.1 (Simply Start).   This parameter should be set to match the horsepower or KW rating of your motor in order for the output scaling to be accurate.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings