Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the Sepam 40 & 80 firmware requirements for setting up the ACE850TP / ACE850FO
Issue
Want to be able to communicate over TCP/IP and was wondering if the old Sepam in the field has the ability.

Product Line
ACE850TP/ ACE850FO

Resolution
The Sepam 40 and Sepam 80 must have a minimum firmware shown in the below table.
ACE850 (TP/FO)Version OK
Sepam Series 40V7.00 or Greater
Sepam Series 80Base & Application V6.00 or Greater

Note: That the ACE850 cannot be used with the Sepam 20 series.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings