Why does the QOGP3P6036 generator panel utilize a 3 pole breaker to switch from utility to generator?
Issue:
Product Design Features

Product Line:
Canadian QO Generator Panels

Resolution:
The Canadian Electrical Code requires the neutral conductor to be switched with the line conductors for a utility/generator application. Therefore, the 3 pole breakers are used to allow both line conductors and the neutral conductor to be switched (or turned ON and OFF) when switching between utility and generator power.