What is the fault rating and momentary withstand capability of HVLCC switchgear?
Issue:
What is the fault rating and momentary withstand capability of HVLCC air insulated switchgear?

Product Line:
Air insulated Switchgear

Environment:
HVL/cc Switch

Cause:
Specification

Resolution:
Current ANSI standards for metal-enclosed switchgear and the components are rated individually in
rms symmetrical amperes. The integrated rating may also be expressed this way (the asymmetrical
rating is obtained by multiplying the symmetrical value by 1.6). For convenience when comparing to
older equipment, the integrated rating is also expressed in “MVA.” The MVA ratings are calculated at
the nominal system voltage and with the rms symmetrical amperes, for example, MVA = Nominal
System Voltage, kV x Amperes rms sym kA x √3.
The integrated equipment rating combines the following ratings:
1. Switchgear—momentary and short-time (bus bracing)
2. Load Interrupter Switch—momentary, fault-closing and short-time,
3. Fuses—interrupting and energy let-through characteristics (current-limiting fuses limit the energy
during a short circuit, thereby allowing higher integrated ratings than the switches and switchgear
would have if unfused)
4. Other components that may have limited capabilities.

NOTE: The testing procedures used to establish the symmetrical interrupting rating set the following maximum withstand ratings for the first half cycle associated with each protective device(1) maximum instantaneous peak let through current (2) maximum single phase rms asymmetrical current at half cycle, and (3) average 3 phase rms asymmetrical current at half cycle.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings