Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I change the direction of rotation on Lexium 32 ?

If you simply want to invert the direction of rotation when the motor makes motion you need to change the parameter called InvertDIrOfMove

The factory default value is set for Inversion Off.   In which case the motor shaft rotates clockwise for positive movements and counter clockwise for negative movements.

By changing this parameter to Inversion On the rotational direction of the motor will be inverted.  Thereby causing the motor shaft to rotate counter clockwise for positive movements and clockwise for negative movements.

The parameter InvertDirOfMove is accessible from SoMove and also via the built-in HMI.

In SoMove you will find this parameter in the section "Axis Configuration > Drive

Via the build in HMI you will find this parameter at "Conf > ACG > InNo

The parameter number is Modbus address 1560

Note that changing this parameter will require you to perform a drive restart  "cycle the power to the drive".



If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings