Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Sepam Running Hours Counter is always 0

Issue:
A Sepam relay is reading 0 for Running Hours Counter. This occurs even when I > 0.1IB. SFT2841 and front display will show a non-zero value for Running Hours Counter but it will also be incorrect.

Product Line:
Sepam S20 S24 S40 S42 S80

Environment:
SFT2841

Cause:
Running Hours Counter is a register only available for Generator relays

Resolution:
There are no available registers in the Sepam 20 series of relays for Running Hours Counter.
The only relays with the Running Hours Counter that will display the value are the generators and motors protection Sepams.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings