Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the InF8 Fault on the Altivar Process Drive?
Issue:
Altivar Process Drive with InF8 Fault.

Product Line:
Altivar Process Drive

Environment:
All serial numbers for Altivar Process Drive

Cause:
Internal supply voltage out of range.

Resolution:
The internal power supplies of the control block are monitored, if one is out of range the INF8 fault occurs.

Remedies
  • Check internal power supply (10V and 24V to COM)
  • Check with SoMove which power supply is out of range.
    • Depending on the result change control block

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings