Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
In Dc cubicle of BlokSeT, is it possible to change Vertical Busbars by Cables?
We do not recommend to replace Vertical busbars by cables in case of Dc cubicles.

In Dc cubicles, the incoming connection to the circuit breaker for each capacitor steps / Functional units are tapped from the vertical busbars. If we remove the VBB, then we have to connect all the cables directly to the HBB. It is very difficult to control the cable bending angle and the cable may not be well supported.

Contact L3 support in case of any doubt.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings