Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are remedies for the Supply Mains Overvoltage Fault (OSF) on the Altivar Process Drive?
Issue:
Supply Mains Overvoltage Fault (OSF) on the Altivar Process Drive

Product Line:
Altivar Process Drives (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar 600 and 900 Process Drive

Cause:
N/A

Resolution:
This fault appears when the nominal voltage exceeds the maximum value of the drive

Possible Remedies:
  • Check Supply Line Voltage
    • Check for Power Factor Correction Capacitors
  • Measure DC Bus Voltage (PA+ and PC-) On an ATV630 these terminals are located behind a black sticker
    • Check for any additional or DC generating device next to the drive
  • If there is an IT system, (High Leg Delta or Corner Grounded), suggest to disconnect the EMI filter and then power cycle the drive and see if the fault returns..
    • Measure each incoming phase to ground to be sure whether you have a high leg. If so, that high leg could be overcharging the EMI filter capacitors, and in turn, overcharging the DC bus


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings