Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
PME - How do I configure WebReach for a 50 Hz system?

For PME 7.2.2 and PME versions prior to 7.2, WebReach requires an additional configuration step if the power system is not 60Hz (for example, 50Hz).  To do this, a user needs add or modify the registry key “LineFrequency” under the WebReach subdirectory of PME.  This key should be assigned a DWORD value of 50(or 0x32 hex) in the case of a 50Hz system.  This value will then be used by WebReach in the calculation of the RMS plot.

Taking PME7.2.2 for example,

aaa

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings