Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Cannot connect to either a M340 or Quantum PLC with Unity 11.1 running in VMWare after updating to Unity 11.1
Issue
Unity fails to connect to the either a M340 or Qunatum PLC after updating to Unity 11.1

Product Line
Unity, M340

Environment
Unity

Resolution
Attempts to to connect to either a Quantum or M340 after updating to Unity 11.1 from Unity 11, could fail if it is installed in a VMware workstation PC..
Prior to updating to Unity 11,1 the problem did not occur.

The following can be used as a workaround.
  • Uninstall the PLCUSB Driver X64 that was installed by Unity 11.1 until a new driver is available.
fdff

  • Insert the Unity 11.0 CD
  • Open the folder named 'Communications Drivers'.
fdsf

  • Double click on the file named 'SchneiderPLCUSBDriverSuite' to install the driver.
sdfd

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings