How is an Analog Output Assignment setup on the Altivar Process Drive?

Issue:
Setting up AQ1, AQ2, and AQ3 on the Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
Altivar Process Drive

Cause:
N/A

Resolution:
To access analog output configurations,
[Complete settings] [Input/Output] [AI/AQ] [AQ1 configuration]

[AQ1 Assignment] AO1 - Analog Assignment - Adjust the analog output assignment (Can be set to motor current, freq, torque etc...)
[AQ1 Type] AO1t - Analog Output 1 Type - Adjust the analog output type between current and voltage

  • Current
    • [AQ1 min output] AOL1 - Analog Minimum Output - Minimum Current Scaling at 0%
    • [AQ1 max output] AOH1 - Analog Maximum Output - Maximum Current Scaling at 100%
    • For example If using 4-20ma out to follow speed reference set the following:
      • AO1 - Motor Frequency [OFr]
      • AO1t - Current [0A]
      • AOL1 - 4
      • AOH1 - 20
  • Voltage
    • [AQ1 min output] UOL1- Analog Minimum Output - Minimum Current Scaling at 0%
    • [AQ1 max output] UOH1- Analog Maximum Output - Maximum Current Scaling at 100%
    • For example If using 0-10v out to follow motor current set the following:
      • AO1 - Motor Current [OCr]
      • AO1t - Voltage [10U]
      • UOL1 - 0
      • UOH1 - 10

Other Settings:
[Scaling AQ1 min] ASL1 - Scaling of the lower limit of the assigned parameter, as a % of the maximum possible variation.
[Scaling AQ1 max] ASH1 - Scaling of the upper limit of the assigned parameter, as a % of the maximum possible variation.
[AQ1 Filter] AO1F - AQ1 cutoff time of the low-filter.

Notes:
Works the same with AQ2 and AQ3
IFrame

*******

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)
ATV600_Programming_Manual_EN_EAV64318_04 - Analog Ouput.pdf [3.99 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings