Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Video: How to program an ATV320 drive to accept start stop from terminals and use AI3 4-20mA as speed control?
Issue:
ATV320 drive to accept start stop from terminals and use AI3 4-20mA as speed control

Product Line:
Altivar 320, ATV320

Environment:
All

Cause:
Programming setup

Resolution:



From RDY, press enter.
Scroll to CONF and press enter.
Scroll down to FULL and press enter.
Scroll down to CTL menu and press enter.
Set FR1 to Ai3 and press enter.
Set CHCF to SEP and press enter.
Set CD1 to TER and press enter.
To scale the AI3 analog input,  go into I/0- (inputs and outputs) menu and press enter.
Scroll to AI3- and press enter.
CRL3 is your min AI3 value.
CRH3 is your max AI3 value.
For example 4-20 would require CRL3 be set to 4 and CRH3 to 20mA.

Note: "press enter" means push in on the dial one time, and "scroll down" means turn the dial clockwise.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings