Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the consequence of a simultaneous action on 2 Solo transmitters ZBRT1 ?
Considering 2 ZBRT1 paired with the same receiver (ZBRRA or ZBRRC or ...), a simultaneous action on both pushbuttons will have the following consequence:
- The gap between the simultaneous actions is less than 10 ms:
--> the orders are lost, no action on the receiver (see IS Expert EIO0000000812 page 51)
- The gap between the simultaneous actions is more than 10 ms:
A/ If the receiver is in monostable status
--> The temporisation of the output is reactivated for 500ms (see IS Expert EIO0000000812 page 55)
B/  If the receiver is in bistable status
--> The status of the receiver is changed (see IS Expert EIO0000000812 page 55)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings