Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
I intend to monitor a system with RM35JA32MW relay at which the current comprises both the AC and DC components. Can the product function correctly?
YES, the product can function correctly.

Below is the front panel setting and waveform diagram.

Ti = Starting inhibit time delay adjustment potentiometer.

Function: On energisation, an inhibit time delay (1…20 s) makes it possible to inhibit (or ignore) current peaks on start-up of equipment.

You can try to adjust the RM35JA32MW product’s Ti setting to inhibit the inrush current during load start-up.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings