Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the specification on the ATV320 Internal +24Vdc power supply?

Article available in these languages: Spanish

Issue:
ATV320 internal +24Vdc power supply specifications.

Product Line:
Drives

Environment::
All

Cause:
Installation / Setup

Resolution:

+24 Vdc, sampling time 2 ms, maximum voltage 30 V, maximum current 100 mA  this supply is used for turning on the logic inputs.

Also note that the P24 is not a input for external supply.   The P24 is a output supply for the STO safe torque off input.

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings