Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What can cause an ETHF embedded ethernet com interrupt fault on the ATV630 and ATV930 process drives?
Issue:
Getting a ETHF embedded ethernet com interrupt fault on the ATV630 and ATV930 process drives.

Product Line:
ATV630 and ATV930 drive

Environment:
All with built in Ethernet

Cause:
Communication interruption on the Ethernet ModbusTCP bus.

Resolution:
Keep in mind that if the PLC or controller is not writing a command or reference to the drive within the programmed TTOB (Ethernet timeout or Hold up time) the Drive can trip on ETHF fault.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings