Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Does the ATV630/930 have a built in time delay feature for digital inputs?
Issue:
Time delay feature for digital inputs in the ATV630/930

Product line:
Altivar Process ATV630 ATV930

Environment:
All models

Cause:
n/a

Resolution:
All of the digital inputs have an ON Delay setting range of 0-200msec.  The factory default is 0msec.
Under Complete settings -> Input/Output -> DI/DQ -> DIx Config, set DIx Delay to the desired time delay.

This delay setting works only as an ON delay, for DIx going active.  There is not a delay feature for OFF delay.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings