How can I configure my ATV630 drive to quickly ramp up to speed when a run command is issued and then operate in PID mode once up to speed?

Issue:
I need my pump motor to quickly accelerate to speed when starting, and then have PID enabled once up to speed.

Product Line:
ATV630 series drives and enclosed versions (660, 680 . . .)


Resolution:
Parameter "PID Acceleration time" under [Complete settings] [Pump functions] [PID controller] [Settings] can be used to achieve this function.   Set your low speed setting (LSP) to the minimum speed your motor needs to run, then set the PID Acceleration time (ACCP) parameter to the number of seconds you want the drive to take to achieve full speed.  (If you want the drive to reach 30 Hz. in 5 seconds, set ACCP to 10.  ACCP is speed to 60.0Hz.  10 seconds to 60 Hz. = 5 seconds to 30 Hz.)   The drive will then follow this acceleration rate until the LSP speed is attained, then switch over to PID mode and follow the 'PID RAMP"  time while in PID mode.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings