Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I prevent an ATV630 from running in reverse?
Issue:
How do I prevent an ATV630 series process drive from running in reverse?

Product Line:
ATV630 series

Environment:
All models, All serial numbers.

Cause:
Information difficult to find in user manual.

Resolution:
Under menu 5, Complete settings, navigate to sub menu 5.5, Command and Reference.  Locate the Reverse Disable parameter and set it to Yes.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings