Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to add TM5SAO4 H/L close to a "high power module" on a TM5NCO1 CANopen island ?
According to documentation TM5SAO4 H/L can not be mounted close to TM5 slices dissipating more than 1.15 W ("high power module" like TM5SPS3) when ambient temperature is more than 55°C.
In this case dummy modules are needed in-between.
But is it OK to do that when ambient temperature is lower than 55°C.

Unfortunalely SoMachine DTM for TM5NCO1 does not take ambient temperature into account and considers worse case only ( > 55°C).

If ambient temperature around your island is lower than 55°C then you can use TM5SAO4 H/L close to modules with power dissipation > 1.15 W. Follow these steps to build your island with SoMachine :
- start with an empty island : TM5SPS3 only
- add a dumy module
- add a TM5SAO4 H/L
- remove the dummy module : an error pop-up appears : simply ignore it.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings