Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
ATV630: How does Normal/Heavy duty affect the Current Limitation in the drive?
Issue:
ATV630 Normal/Heavy duty Current Limitation.

Product Line:
Altivar 630, ATV630

Environment:
All

Cause:
n/a

Resolution:
Go to menu 5.2 ( Motor Parameters), select Dual rating, then select:
Normal duty current limit is 1.1 of In
Heavy duty current limit is 1.5 of In.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings