For I-Line Panels with Electornic trip Mains where does the 24 VDC power supply connect to , Line , or load side of Main?
Issue:
Line Side Connection on 24 VDC power supply on I-Line Panels with Electornic trip Mains

Product Line:
I line Panelboards

Environment:
Installation

Cause:
Wiring clarification

Resolution:
The connect should to the Line side of the breaker so that if breaker trips, the power supply will still operate the display indicating Why breaker tripped