Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
PME 8.2 Web Applications stuck at settings tab
Issue
User is attempting to log in to PME 8.2 web applications using the correct user name and password but being redirected to the settings tab automatically. None of the other web applications tabs are showing up to be able to navigate to.

Product Line
Power Monitoring Expert 8.2

Environment
Web Applications

Cause
In PME 8.2, the Settings tab is the only one that does require a licensing check, so if the licensing check fails, you are redirected immediately to the Settings tab.

Resolution
1) Verify that your PME 8.2 system is licensed properly.(For a video article on How to look up information about a Power Monitoring Expert (PME) license using the Activation ID or Entitlement ID, click here)
2) If software is licensed and you are still expericing this issue, restart lmadminSchneider windows service.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings