Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Does a 5.0P or 5.0H trip unit have a ground fault alarm indicator on the LED display screen?
Issue:
Is there a ground fault alarm indicator on the trip unit itself?

Product Line:
Circuit breakers

Environment:
Micrologic 5.0P and 5.0H trip units

Resolution:
No, there is not an indicator on the trip unit itself. Also, the trip unit LCD screen gives no indication when the ground-fault pickup has been reached.  The GF alarm can only be indicated by:
1) sending the signal through the M2C or M6C contact block, or
2) reading the GF alarm through Modbus Register if available.  See FA306313 for more information on reading ground-fault alarm through Modbus.
3) trip unit alarm history (wrench button, go to history logs, then scroll to alarm history)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings