Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is the Model 6 motor control center (MCC) available for a 240V delta system with a high leg?
Issue:
Can you get a MCC rated for a 120/240 3 phase 4 wire high leg system?

Product Line:
Motor Control Center - MCC

Environment:
Model 6

Cause:
Application requirement delta high leg

Resolution:
In Product selectors, the MCC would be entered as 240 v 3Ph 3W. This way the CPT's in the units will be correct. You must put a note in the "Gen Req" tag window- "This is a 240 volt 4 wire with a B-High leg". The plant will then mark this and add a red sign on the MCC about the High Leg. You will need to identify which phase is the high leg. Please be reminded this may impact the delivery code.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings